INDUCTION, GROUNDING AND BONDING
OBJECTIVE
You will identify a variety of Induction Hazards and state how to eliminate or
control them through the use of specific barriers.
You
will learn on how install a set of cluster and/or jumper temporary grounds
following approved grounding procedures and state when, where, and why
temporary grounds are used on distribution lines.
INDUCTION HAZARD
Induction
is the transfer of electric energy from an energized line to an isolated line
through a magnetic or electric field.
In
general, there are two kinds of induction: Magnetic Induction
(sometimes
referred to as electromagnetic induction) and Electric
Induction
(sometimes referred to as electrostatic induction).
Even
though a distribution line may be disconnected or isolated from an electrical
source, it is still not safe to work on until it is properly tested for
potential voltages and grounded.
Before
grounding, the line can still have hazardous changes on it because of
induction. After grounding, a hazard can still exist if they are not spaced
properly.
Factors
that affect the strength of induced charges are:
a) The
amount of current (amperage) and voltage on the neighboring energized line. The
higher the amperage and/or voltage, the higher the (Induction) on the isolated
line.
b) The
distance between the isolated and energized line. The closer the lines, the
greater the induced charge.
c) The
distance the isolated and energized lines run parallel to
each other. Lines that run parallel for a long distance result
in a higher induced charge than for shorter runs.
d) The
size of the conductor is also a contributing factor. The larger the surface,
the greater the induced charge.
Many
lines you work on are not greatly affected by induction and as a consequence it
is easy to forget about the hazard it poses. The hazard of induction is very
real, and generally presents itself when those working on the lines have in
fact, forgotten about the hazard and have not taken proper precautions to guard
against it. In order to eliminate this hazard, approved grounding, bonding and
jumpering techniques must always be used when working on isolated lines.
The
concept of induction is explained in every electrical book you will ever read,
but words on printed page often don't convey the message as meaningfully as
they should. If you ever work with grounds on one isolated circuit of a double
circuit 230 kV line, you know induction is very real. The arcing that often
takes place when a ground clamp is removed is enough to convince anyone that
induction isn't to be fooled with.
TEMPORARY GROUNDS
In
this part you will learn about installing temporary grounds, which are safety
devices to protect you at the work site from the hazards of induction. You will
find out what "grounds" are, why and when they are used, and how they are
applied to an overhead distribution line, and for work-vehicle pounding.
The
basic purpose of grounding in an electrical system is to ensure components that
may be touched or worked on are at the same potential as the surrounding earth
(approximately zero volts). This makes it generally safe to approach and touch
the component.
You
achieve grounding by metallically connecting whatever you wish to "ground", to
a suitable ground electrode (i.e., system neutral, etc.). You may ground on a
permanent basis, such as in a substation, where all non-current carrying
components such as structures, metal parts of buildings etc., are solidly and
permanently connected to bare cables buried in the earth. Alternatively, you may wish to ground
conductors, equipment, or apparatus only for the period of time they are being
worked on. In this case temporary grounds are used.
Pike
Electric, Inc. Safety & Training Manual
Section 4
OHD Distribution & Transmission 410
DE-ENERGIZING
LINES
A. ELECTRICAL
CONDUCTORS MAY BE WORKED AS DEAD (DE-ENERGIZED) UNDER THE FOLLOWING CONDITIONS:
1. The
line must be de-energized in such a manner that a visible opening exists
between the source and work location and then checked to assure that no power
is on it.
i. The
line may be opened, load permitting, with a loadbuster, a disconnect, a fused
switch, or by removing a tap jumper.
ii. De-energizing
a line by opening a recloser or a sectionalizer, will not suffice as a visible
opening.
2. Primary,
as well as secondary lines and equipment may not be worked as dead unless
flagged, tagged and adequately grounded (See 410B). The de-energized line must be grounded to the
system neutral, an appropriate flag installed on the same structure, and tags
attached at all points where equipment or circuits can be energized.
B.
PROCEDURE FOR GROUNDING OVERHEAD LINES
1. When
attaching grounds, always fasten the ground connection first and the circuit
connection(s) last. When removing
grounds, always remove the circuit connection(s) first and the ground
connections last.
2. A
grounding lead (including attached clamps) shall be capable of conducting the
anticipated fault current and shall have a minimum conductance of No. 2 AWG
copper.
3. Every phase must
be grounded. When the de-energized line
consists of more than one phase conductor, the grounds shall be installed so
that the
3-phase line is short circuited.
4. Grounds
shall be installed and removed from current carrying conductors with approved
live line tools.
5. When
attaching grounds, do not allow your body to come in contact with the ground
wire.
Note:
When grounding de-energized transmission lines, the grounds should be placed
outside the work area when possible, in addition to placing personal protective
grounds at the point where the work is being done.
C. The
foreman or other employee in charge shall inform the members of his crew when
the line is de-energized and grounded. Before the line is energized again, the employee in charge must inspect
the line and all the members of the crew shall be informed.
DISTRIBUTION CIRCUITS
There
are two terms which you should be very familiar with and be able to distinguish
between.
"Isolated"
- the line has been physically disconnected from its
usual
source of power. It does not mean it is safe to touch.
"De-energized"
- a line is considered de-energized ("dead"), and safe to touch, only after it
has been isolated and grounds have been applied.
Isolated
distribution circuits may still carry a hazardous voltage.
This
can be due to one or more of the following:
- The
circuit could be energized accidentally if someone violated protection tags and
improperly operated a switch; or by contact with a live conductor such as might
occur if a vehicle collided with a pole.
- Induced
voltage on the conductor due to the circuit paralleling an energized circuit.
- Lightning
may strike the circuit. (All work on any circuit should be stopped when
lightning storms are in the vicinity
(i.e., 15 miles).
- Natural
phenomena such as electrically-charged storm clouds in the vicinity, or wind
blowing across it can induce
electrostatic charges on the circuit.
- A
backfeed may exist as from a customer's portable generator.
Since
there is uncertainty as to the potential on an isolated circuit,
all
circuits must be treated as energized until adequately grounded.
The
main reasons for grounding isolated overhead circuits are:
- To make certain they are de-energized
before starting work.
- To
ensure fast clearing of the circuit should it become energized.
Always
positively identify the neutral. It has occurred that a conductor, even when in
the secondary/neutral position has actually been a live phase conductor. It is
therefore necessary to positively identify the wire in the neutral position as
being connected to ground. It may be necessary to travel a number of spans in
either direction to a location, such as a transformer, to insure the neutral is
connected to ground. If it is not possible to identify the neutral in this
manner, then a ground must be applied at the work location.
The
shotgun stick is probably the most frequently used live-line tool by the line
crews. It is like a hand on the end of a live-line tool which enables the
worker to grab, position, tighten, and remove energized pieces of equipment It
is used to install and remove live-line clamps and ground clamps, and to
operate switches and pull loadbreak elbows. You will use it to install
temporary grounds to de-energize a three-phase distribution line using both
jumper and cluster grounds.
Temporary
grounds are applied to de-energize conductors and
equipment
to protect personnel from the hazard of electrical shock.
GROUNDING EQUIPMENT
Grounding
equipment for overhead lines must be of a satisfactory arrangement and be easy
to apply. They must meet the requirement of all field application conductions,
utilize minimum time and preparation for installation, and must accept a wide
range of conductor sizes and configurations. The 4/0 copper tap should be
chosen for its continuous current carrying capacity of 400 A as well as its
mechanical strength and size to fit the conductor.
The
clamp must have adequate electrical capacity to withstand e maximum fault
current (30,000 A) available for the full time
duration
over which that current may flow.
Two
major considerations should be met in choosing the cables.
- The
terminal capacity should be such that there is a good mechanical and electrical
connection between clamp and
cable.
- The
criteria in choosing the proper size cables are the maximum fault current which
can be realized on the system and time duration of that current for general
utility purposes, it is felt that 1/0 copper flexible cable should be the
minimum size.
Due
to varying configurations in construction and different applications, the trend
in temporary grounding arrangements is for individual jumpers. The jumper sets
comprise of three short pieces of cable, ranging from 6 to 12 feet in length,
with the appropriate clamps connected to each end of the jumper. Depending upon
the application, there may be a need for a longer piece of cable which could be
connected from a ground probe to the system neutral or a grounding cluster
support.
The
cable used in the sets can have a neoprene rubber outer jacket or a
polyvinylchloride clear covering. With the clear covering, the condition of the
strand can be inspected, especially at the point of
connection
of the clamp where there is considerable stress from constant use.
In
the preparation for temporary grounding of overhead lines, it is fundamental
that before considering any conductor or equipment as dead or de-energized, it
must be properly grounded. A generic definition of work on de-energized lines
is as follows:
Working
on De-energized Lines
1. Temporary grounding devices of adequate
current carrying
capacity
shall be placed on conductors between the work location and all possible
sources of electrical energy before said conductors may be considered
de-energized.
2. Temporary
grounding devices shall be installed with a live-
line tool, only after
potential tests have been completed to
ensure that said conductors
are isolated.
3. Temporary
grounding devices shall be placed so that one set is readily visible to at
least one member of the crew at
all times.
4. Places
where the de-energized line crosses, is crossed, or is adjacent to another
circuit shall be considered a possible
source of energy.
5. Suitable
temporary grounding devices shall be first connected to a low resistance ground
before being brought in contact with any isolated conductor of the circuit to
be grounded. They shall be removed from all circuit conductors before being
disconnected from ground.
PICK
A GOOD LOCATION: If at all possible
temporary
grounding
devices should be installed at the pole on which work is being performed.
However, these should be placed well outside the immediate work area, the
reason being that serious injury could result from the violent movement of the
pounding cables under high fault current conditions. Likewise, to prevent
accidental contact good judgment should be exercised with regard to the use of
temporary pounds on poles where there is live equipment such as transformers,
switches, reclosures, etc.
TESTING
FOR POTENTIAL: After one has
received confirmation that isolation of the circuit has been carried out, the
worker should then perform an approved test for potential on the isolated
circuit Isolation may not have been complete and contact may have been made
between the isolate circuit and other energized circuits in the area. Failure
to perform a test for potential in an approved manner could result in the
worker attempting to install grounds on an energized circuit.
Teasing
the isolated conductor with the metallic end of an approved live-line tool
should not be used as a test for potential. On low voltage distribution
circuits this charging current might not be seen or heard. On higher voltage
distribution circuits, the charging current may only be induction from other
live circuits and possibly mistaken for actual line potential.
CLEANING
THE CONDUCTOR AND EQUIPMENT: Cleaning the conductor by approved methods
before installing temporary grounding equipment is very important. The surfaces of conductors are usually
contaminated or corroded. In some cases, equipment or metal structures are
coated with paint. This high resistance
surface contamination must be eliminated with an approved conductor cleaning
wire brush or filing process to ensure positive contact with the surface to be
grounded. Consideration might also be given to the use of clamps with serrated
jaws; however, these clamps should not be used on aluminum conductors unless a
"split sleeve" or "stirrup" has been installed prior to applying the grounding
clamp.
MINIMIZE
CABLE SLACK: Shorter grounding
cables offer lower resistance. Tremendous forces are involved during fault
currents which result in severe and dangerous cable movements if there is
excessive clack in the grounding cable. Long leads should be lashed at some
intermediate point to reduce the hazard to personnel and dislocation of
grounding connections.
CHOICE OF GROUND ELECTRODE
When
grounding a circuit, it is very important that the ground electrode with the
lowest possible ground resistance be used, provided this can be done safely. A
high ground resistance can create hazardous step and touch potentials near the
ground electrode. A high ground resistance may also prevent protective
equipment from automatically isolating the circuit if it is still energized or
accidentally becomes energized.
Note: Permanent ground network (e.g., system neutral, station ground network),
To
ensure a good connection is made, use a wire brush to clean a section of the
temporary ground rod where the ground connection is to be made.
HANGING PORTABLE GROUNDS ON THE POLE
The
lineperson will secure the handling approximately 1 m (3')
below
the neutral (when the neutral is in the secondary position or below the crossarm
brace irons when the neutral is on the crossarm). He may drive the shank of his
screwdriver into the pole (blade is inserted against the grain of the wood)
approximately 25 mm (1"), this will prevent the handline from sliding
down the pole. A small rope sling is wrapped twice around the pole and tied
approximately 150 mm (6") above the handline sling and may be used to support or
hang the cluster of portable grounds. A snubbing bank may also be used to hold
the grounds.
The
grounding clamp shall be installed on the conductor by means of an approved
insulated hot stick using rubber gloves. It shall first be poised above the
conductor and then placed quickly and firmly on the conductor and tightened. In
performing this operation, care shall be taken to avoid "teasing" the conductor
with the clamp. If, due to some mistake, the circuit is energized, the clamp
shall not be withdrawn once it has made electrical contact with the conductor
as this will create an arc which would result in serious injury to the worker.
Pike Electric, Inc. Rules in Grounding
B. PROCEDURE FOR GROUNDING OVERHEAD LINES
1. When
attaching grounds, always fasten the ground connection first and the circuit
connection(s) last. When removing
grounds, always remove the circuit connection(s) first and the ground
connections last.
2. A grounding lead (including attached clamps)
shall be capable of conducting the anticipated fault current and shall have a
minimum conductance of No. 2 AWG copper.
3. Every phase
must be grounded. When the de-
energized
line consists of more than one phase
conductor,
the grounds shall be installed so that the
3-phase
line is short circuited.
4. Grounds shall be installed and removed from current
carrying conductors with approved live line tools.
5. When attaching grounds, do not allow your body
to come in contact with the ground wire.
Note: When grounding de-energized transmission lines, the grounds should be
placed outside the work area when possible, in addition to placing personal
protective grounds at the point where the work is being done.
c. The foreman
or other employee in charge shall inform the members of his crew when the line
is de-energized and grounded. Before the
line is energized again, the employee in charge must inspect the line and all
the members of the crew shall be informed.
INSTALLATION SEQUENCE
For
the installation of jumper grounds on armless framing, proceed as follows:
a) Ensure that for
each jumper
one snap-on
eye screw clamp
is seated
securely on the
support stud
of the other
snap-on eye
screw clamp,
Figure 4.
Figure 4
b) Identify the
neutral and
connect a
jumper to it.
Remove the
other end of the
jumper from
the support stud
and connect it to the phase
conductor
closest to the
lineperson,
Figure 5.
Figure 5
c) On multi-phase
circuits,
grounds are
then applied from
a grounded
phase to an
isolated
adjacent phase,
Figures 6 and
7.
Figure 6
Figure 7
For
the installation of jumper grounds on flat construction proceed as follows:
a) Ensure
that for each jumper, one snap-on eye screw clamp is seated securely on the
support stud of the other snap-on
eye screw clamp.
b) Identify the
neutral and
connect a jumper to it,
Figure 8. Remove the other
end of the jumper from the
support stud and connect it to
the closest phase conductor,
Figure 9.
Figure 8
NOTE: If each clamp, equipped
with the stud, see Figure 3,
is placed on the conductor
directly above the lineperson,
they are much easier to remove.
c)
On multi-phase circuits,
pounds are then applied
from a grounded phase to
an isolated adjacent phase,
Figures 10 and 11,
Figure 9
Figure 10
Figure
11
TEMPORARY GROUNDING OF VEHICLES
It
is imperative that all digger derricks and aerial bucket devices (with lower
metal booms) be grounded to the system neutral when used in close proximity to
overhead conductors. Just as important is the fact that all personnel, plus the
general public be kept clear of the line vehicles during these operations, with
the exception of the worker who might be operating the controls of a digger
derrick. No harm would come to them as long as they remain on the operator's
platform or on a ground gradient control mat bonded to the truck frame.
Even
though the truck ground has been connected to the multigrounded system neutral
- a worker or someone from the general public at ground level while in contact
with the truck body would create a parallel path to ground, should the boom
make contact with overhead energized equipment. The person could be subjected
to lethal currents (see Figure 12).
Figure 12
The
duration of contact to the energized vehicle would be of a very short period
and isolation would be almost instantaneous, that is assuming hold-off
protection was in effect. Grounding to the multi-grounded system neutral
ensures rapid isolation of that circuit by providing a low resistance path
through which enough current can flow to operate circuit protection devices,
thus releasing a victim from sustained contact, as well as returning the work
area to a relatively safe condition.
However,
the initial contact by the worker or member of the general public with the
truck could prove fatal if the right conditions were present. Remember, even
though a truck ground is used, keep the workers and the general public clear of
the vehicle when the boom is in close proximity to overhead energized
equipment.
The
following illustrates the safe limits of approach when
operating
boom-equipped vehicles.
Pike Electric, Inc Safety &
Training Manual Section 12 Tables
TRUCK GROUND EQUIPMENT
All
truck grounds should comprise of at least 1/0 flexible copper cable and is
capable of being attached to the overhead system neutral. One end of the cable
would have an appropriate current carrying capacity grounding clamp. It is
preferred that the other end of the cable would be solidly and permanently
connected to the truck frame, for example, a compression type lug fitting.
All
components of the vehicle should be bonded together, such as
the
chassis and frame, etc.
Figure
13 Figure 14
Pike
Electric's method is to simply utilize hangers attached to the rear of the bin
structure to store the grounding cable when it is not in use (Figute13). Some
feel that the truck grounds should always be at the rear of the truck,
especially with a digger derrick, as a constant reminder to the operator of the
dire need of grounding the truck when the boom is used near live apparatus.
Note: When truck ground is being used always pull truck ground completely off
of rack.
>SKILLS CHECK REVIEW
1. Induction
is the transfer of electric energy from an energized line to an isolated line
through a ________or ____________.
2. What
is defined as "Isolated"?
3. What
is defined as "De-energized"?
4. According to Pike's Safety & Training Manual what
are considered good ground sources and what order should be utilized for
distribution?
a. _________________________________________.
b. _________________________________________.
c. _________________________________________.
5. A
screw ground may only be used when a better ground source is not available and
approval has been given by the immediate supervisor or employee in charge.
True or False
6. Temporary grounding devices shall be
installed with a__________, only after potential tests have been completed to ensure
that said conductors are isolated.
ANSWERS TO REVIEW
1. Magnetic
or electric field.
2. "Isolated"
- the line has been physically disconnected from its usual source of power. It
does not mean it is safe to touch.
3. "De-energized"
- a line is considered de-energized ("dead"), and safe to touch, only after it
has been isolated and grounds have been applied.
4. The following are considered good ground sources and
should be utilized in the order listed below:
a. The
system (common) neutral located on the same level or above the energized
conductor(s).
b. Pole grounds (if tapped to system
neutral)
d. Guy wires (if
tapped to system neutral)
5. True
6. live-line tool
RUBBER PROTECTIVE EQUIPMENT
OBJECTIVE
You will identify and inspect a variety of rubber
protective equipment and review their working voltage and job application.
Rubber gloves are the most important of all the
protective devices you will use as a lineman. As a first line of defense, they
protect you from energized apparatus. That is why it is extremely important you
know what class of glove to use on what voltage, how to inspect them and how to
care for them.
TYPE OF GLOVES
Rubber gloves are available in four classes. Use the
glove suited to the voltage range you are working on:
VOLTAGE
Maximum Use
Voltage
Note: Rubber
gloves shall be laboratory retested per OSHA standards of "in-service use". No
test period shall exceed six months of combined in-service use and shelf life.
The test voltage for each class of glove is
determined by the manufacturer to build a safety factor. Since this electrical
test is done in a laboratory under controlled temperatures, filtered air and
humidity conditions for only one minute, under no circumstances should test
voltage be confused with actual working voltage.
Note: Rubber
gloves shall never be used beyond the expiration date.
Class No. 3, 4 - Rubber
Glove Work must be performed from an approved insulated work platform or aerial
device. Class No. 2 –Rubber Glove work from pole is accepted with some
customers.
The class of rubber glove is
identified by the testing lab stamp which appears on the cuff of each glove.
This stamp includes date of last test and test voltage and is the only certain
way to be sure the gloves are, in fact, a specific class as other classes of
gloves are very similar in construction and design.
Most rubber gloves are bi-colored with a black rubber
surface and either a yellow or red inside surface and cuff. They may be five
fingered or mitten type. The two-color fabrication of these gloves lets you
readily identify points of wear or other defects in the outer black surface
when the glove is inflated during the inspection and air tests.
Rubber gloves are always worn with protective covers.
These covers consist of a leather glove combined with a cuff of synthetic or
leather material. This cuff should not be relied on for electrical protection.
The covers are sized to fit over the same size glove, i.e., size 10 cover for a
size 10 glove. When the covers are on the gloves 1-1/2 to 2-1/2 inches of
rubber glove should be visible above the rubber glove protector. This provides
extra leakage protection.
Each time you go to use your rubber gloves, inspect
and air test them, the following procedure. Stretch the glove to look for
cracks and tears. Reverse the glove and do the same on the other side.
Look for punctures, hard spots, foreign material or
breaks in the surface. With the two colors, these abnormalities are usually
easy to see.
Minor cuts and abrasions to the outer black surface
of the glove are permitted if the contrasting inner color does not show
through.
The inner yellow or red part of the glove represents
80% of the glove thickness. it is not possible to determine in the field just
how deep a cut or abrasion may be, therefore, any break in the inside surface of the rubber glove renders the glove defective. It must be returned to
the work location for replacement.
If the gloves are all one color (black) inside and
out, any break in the surface would render them suspect and they must be sent
back for retesting.
Both the air test and the visual tests are needed.
Air tests tell you if there is a puncture, visual tests tell you if there is
excessive wear. You can then replace the gloves before a hole is apparent.
Twirl the glove to fill it with air and trap it by
rolling the glove cuff. With your free hand, squeeze the glove in various
places. This inflation of the glove will amplify any small damaged spots which
might not be found by ordinary visual inspection. While the glove is inflated,
hold it up to your face to feel or hear if any air is leaking through a
puncture.
Rubber glove protectors should be inspected once a
day before using. Look for any wood or metal splinters which could puncture the
rubber gloves. If the covers are oil or penetrox soaked, or worn through in
spots, they should be replaced. They must adequately protect the rubber glove,
and in turn, you. A cut through the leather or synthetic part of a glove cover
should be investigated to see if any damage has been transferred to the rubber
glove inside the cover.
CARE OF RUBBER GLOVES
Take the following precautions:
(a) Do not wear projecting rings or watches
under your rubber gloves. Electrical Research advises many gloves show
indications of corona cutting where these items contact the gloves.
(b) Do not store or use rubber gloves turned
inside out. The reversal from the original set of the rubber sets up a sufficient
stress to induce severe checking under the influence of ultraviolet rays from
sunlight and fluorescent lights, or ozone from live electrical apparatus.
(c) Do not store gloves in substations or
other locations where there is a likelihood of corona or spark discharge. A
very small concentration of ozone causes rapid oxidation.
(d) Do not
store gloves in a compressed, creased, or folded position. Protect them from
damage by storing them cuffs down, in the approved canvas bags, when not in
actual use. Close dome fasteners to protect against dirt, sunlight, and
fluorescent lights.
(e) Gloves
may be cleaned in the field using only clean water. Do not use soap, detergents, or other
cleaning agents. Cornstarch may be used to help put on the gloves.
(f) Gloves can be seriously damaged by
grease or oil. Avoid contact with these substances. If the gloves inadvertently
contact these substances, return them to the work location for replacement.
CORONA
CUTTING
Air around energized electrical equipment becomes
ionized or broken down into its basic components, one of which is ozone gas.
The higher the voltage at which the electrical
equipment operates, the greater volume of air is ionized. Ozone destroys
natural rubber, the main component of your rubber gloves. The rate at which
rubber gloves deteriorate in the presence of ozone gas is proportional to the
amount of stress placed on the rubber. The effects of ozone damage or corona
cutting depends upon the concentration of ozone, the amount of mechanical stress,
and the duration of exposure.
Each class of glove has a composition of rubber
designed to withstand ozone levels present at the glove's maximum working
voltage. This takes into consideration the duration of rubber glove jobs and
mechanical stress caused by finger and hand flexing. If a rubber glove is used
on a voltage higher than its voltage rating, excess ozone at the higher voltage
level, combined with mechanical stress from your hands, causes rapid rubber
deterioration.
You will be using your rubber gloves for such jobs as
operating handlines, taking voltage checks, connecting secondary services and
when working on any pole supporting a live conductor. The Ground-to-Ground Rule
may apply to some of our customers.
3. * Approved rubber gloves:
a) are worn only with protectors
(leather gloves over the rubber ones).
b) shall
be worn when on any pole or other structure on which energized equipment is
located or when equipment on the pole is being worked as energized or when
equipment on the pole is being worked as energized or when the employee is
within 6 feet of any such equipment.
c) shall
be worn while climbing up or down poles if any energized equipment or equipment
that could become energized is on that pole. The same holds true for any other type structure.
c1) shall be
worn and used for primary employee protection when used in conjunction with
live line tools.
d) shall always be
worn when working in buckets within six feet of any energized equipment, or
equipment that could become energized.
*
Glove Classification shall correspond to the voltage being worked (See Table 2A
Section 12)
e) must
be used when painting poles when you are within 6 feet of energized equipment.
f) shall be stored in rubber glove bags when not in use.
NOTE: Some of
our customers require that we wear rubber gloves all the time while aloft in
buckets.
g) shall be
air tested each day prior to use.
h) shall be
exchanged each month and returned to
Mount
Airy,
NC where they
will be washed and thoroughly tested.
i) shall be worn
when involved in such tasks as pulling guys, pulling wire, and setting poles
when any part of the work is in close proximity to energized conductors or
conductors that could become energized.
j) may be removed
while near energized equipment, after the equipment ahs been fully covered with
rubber goods, under the following circumstances:
(1) when changing internal transformer taps on de-energized transformers
(2) when
removing particles from one's eye
(3) when removing small articles from nut bag
(4) when lighting a cigarette
(5) when having something to drink or eating a snack
*BEFORE the employee removes his gloves, he must
place himself in a position beyond reaching distance from any energized
conductor or equipment and then notify either and employee on the ground or
another lineman on the same pole or structure of his intentions and receive a
reply from the other person. While
rubber gloves are removed, the employee shall not change his position. Before returning to work, he must inform the
other employee that he has replaced his rubber gloves and is ready to return to
work and must receive a reply from the other person.
NOTE: DO
NOT USE ANY HAND CLEANER ON THE JOB THAT CONTAINS AMMONIA. THIS TYPE OF CLEANER DAMAGES RUBBER GLOVES.
F. Upper Arm & Shoulder Protection
Rubber sleeves:
1. shall be
worn only in conjunction with rubber gloves with the cuff inside the gloves.
2. shall be worn anytime an employee is working on
energized equipment that is energized at over six hundred (600) volts or within
reaching distance of such equipment.
3. shall
be worn by employees who are within reaching distance or above or must move
past equipment energized at over 600 volts. On poles with energized primary conductors, the lineman or employee must
put on sleeves when he climbs above the point where his safety belt attachment
would be above any secondary conductor or the common neutral. (This same rule
applies to work done from buckets)
NOTE: Some or our customers require us to wear
sleeves all the time while aloft in buckets.
4. shall
be examined prior to use for any obvious holes or any damages that may have
occurred. Turn in any damaged sleeves to
your supervisor immediately.
5. shall
be inspected each day prior to use.
6. shall be exchanged every two months and returned to
the
Mt.
Airy, NC Office where they are washed
and thoroughly tested.
F1. Rubber
sleeve straps shall be worn over shoulders of employee.
G. Leg Protection
Approved rubber climber guards shall be worn on all
climbers. When rubber climber guards
become worn you shall request a new pair from your supervisor.
H. Foot
Protection
1. Pike overhead distribution line employees shall wear approved
hard-toed work boots or an approved workshoe that offers protection to the feet
and ankles.
2. Line
workers shall wear approved, rubber overshoes or rubber boots when working in
the vicinity of any energized lines or equipment, or when any conductor being
worked on could contact the worker if it should fall. It is extremely important that employees
working on the ground as well as in the air wear overshoes for protection from
both direct and indirect acci-dental contacts. (Overshoes shall not be relied
on as primary protection. The are incidental protection only.)
|
|
EXCEPTION
Employees are not
required to wear overshoes when performing work from an insulated Aerial
Bucket.
|
|
3. When rubber overshoes or boots become worn you shall
request a new pair from your supervisor. To receive a new (company-furnished) pair of overshoes, turn in the worn
pair to the supervisor.
4. Follow all rules listed under Section 119 G.
I. Clothing
Pike employees exposed to flames or arcs shall:
1. wear
a flame retarded vest (provided by Pike) as protection for the upper portion of
their body. The vest shall be worn as
the outer garment.
2. wear
flame retardant, or denim pants as protection for the lower portion of their
body.
J. Jewelry
Loose, dangling watch
chains, key chains or unnecessary metal of any kind shall not be worn when
working on or near energized parts or parts that could become energized.
INSPECTION OF HOSE, HOODS, AND BLANKETS
Line hose is inspected on the inside as well as the outside.
To examine the inside, spread the hose open and hold it between your hands.
With a little practice, the hose can be rolled or peeled, from end to end. With
the crown of the bend held close to the eyes, watch for soft spots, hard spots
or cracking which indicates that the insulation value of the hose has
deteriorated. If these faults are detected, do not use the hose. Punctures and
cuts more than 114 the depth of hose renders it defective. File if necessary to
check depth.
Insulator hoods are inspected both inside and out. To inspect the
inside surface, the hood may be opened wide by bending across the knee. Watch
for soft spots, hard spots, or cracking which indicates that the insulation
value of the hood has deteriorated. If these faults are detected, do not use
the hood. Punctures and cuts more than 1/4 depth of hood render it defective.
File if necessary to check depth.
Blankets are inspected by rolling them on a flat surface. A
careful examination cannot be made by glancing over the flat surface. Watch the
top of the roll for cuts, snags, or other damage. To effectively check a
blanket it must be rolled and inspected four times. Roll from one corner to the
other. Turn blanket 90° and repeat Turn blanket over and repeat the two-roll
procedure.
Any break in the surface, inside the button hole
area, shall be
considered a defect and the blanket must be returned to the
Electrical Testing Department for electrical retest If the blanket
passes the retest, the minor surface break will be buffed away and
the blanket will be date-stamped and returned for regular use.
CARE OF HOSE, HOODS AND BLANKETS
Observe the following:
(a) Hose, hoods and blankets may be cleaned
at your utility using the following approved method. Hose, hoods and blankets
are soaked in a solution of hot water and an approved cleaning solution for 15
minutes at a temperature of 1200F to 1400F. Soil can then
be wiped off with a rag. The inside of the hose can be cleaned with a two-inch
bottlebrush. Drain. Immediately rinse
off using running water inside and out for one minute. Allow to dry.
(b) Crease marks, caused by lasting folds,
sharp bends or continued distortion, set up a stressed condition and invite
corona damage wherever this rubber equipment is held under tension. Blankets
shall always be laid flat while in storage or rolled and stored in approved
containers. Line hose should not be stored in a bent condition or folded to fit
in a truck compartment.
(c) Blankets shall be electrically retested
before the Electrical Testing stamp's expiration date.
(d) Line hose or blankets should never be
used to insulate one conductor from another. These articles are designed and
intended for personal protection only. The combination of mechanical stress and
voltage can damage the protective equipment to a point that would make them
unsafe for further use.
(e) To
reduce the friction and help the line hose slide more easily onto the
conductor, the inside of the hose may be
powder with cornstarch
or Manufacture's recommended powder.
406 LINE PROTECTIVE EQUIPMENT
A. GENERAL
1. When work is to be done on or near
energized lines or equipment all energized and grounded conductors or guy wires
within reach of any part of the body shall be covered with rubber protective
equipment, except that part of the conductor to be worked on.
2. In
applying rubber protective equipment, an employee shall always cover the
nearest and lowest wires first, protecting himself as he progresses. In removing rubber protective equipment, the
reverse order shall be maintained.
3. To avoid corona
and ozone damage, do not leave rubber protective equipment on energized lines
or apparatus overnight of for more than one 10 hour period, unless approved by
the supervisor in charge.
4. Rubber line hoses, blankets, and/or hoods, shall
be used to cover all energized equipment within reaching distance of employees
except for that being worked on.
5. Rubber line
hoses, blankets, and/or hoods shall be examined prior to use for any obvious
holes or any damages that may have been incurred. Damaged rubber protective equipment shall be
turned over to your supervisor immediately.
B. APPROVED
RUBBER LINE HOSES
1. Shall be exchanged every 12 months and returned
to the
Mt.
Airy, NC office where they are
thoroughly washed and tested. Each crew
is supplied with line hoses. If the
employee in charge sees the need for additional line hoses, he should request
them from the area supervisor.
C. APPROVED
RUBBER BLANKETS
1. Shall be
exchanged every 12 months and returned to the
Mt.
Airy,
NC office where they are thoroughly washed and tested.
2. Should be
rolled, not folded for storage. Each
crew is supplied with rubber blankets. If the employee in charge sees the need for additional rubber blankets,
he should request them from the area supervisor.
SUMMARY
Working on energized lines using rubber gloves is a
common activity in your job as a lineman. The gloves you wear and the cover-ups
you use protect you from injury due to contact with a conductor. You must know
how to use them well.
In using gloves make certain you use the right glove
for the situation. Always check the cuff to ensure you in fact have the correct
class. Wear a cover over your gloves and store them correctly to prevent
accidental or accelerated deterioration. Be certain you do a safety check every
day.
Note: Baby Powder should not be used in
rubber gloves. The
perfume
in the powder is conductive and some perfumes
have
oil-base additives which deteriorates the rubber.